Site Tools


ge:prime-vs-standby

Differences

This shows you the differences between two versions of the page.

Link to this comparison view

Both sides previous revisionPrevious revision
Next revision
Previous revision
ge:prime-vs-standby [2013/01/24 16:40] – ge:diesel-generators:prime-vs-standby renamed to ge:prime-vs-standby Alan Sheage:prime-vs-standby [2024/06/27 19:27] (current) – [:: COP :: Continuous Power or Baseload Power] Alan Shea
Line 7: Line 7:
 We recommend purchasing generator sets based on the Prime Power ratings, even when they will be used for standby power in developing countries. This will result in longer life and better return on the investment.  We recommend purchasing generator sets based on the Prime Power ratings, even when they will be used for standby power in developing countries. This will result in longer life and better return on the investment. 
  
-====Prime Power===+====:: PRP :: Prime Power===
 <blockquote John Deere, Generator Drive Engine Specifications> <blockquote John Deere, Generator Drive Engine Specifications>
 The prime power gen-set engine rating is the nominal power an The prime power gen-set engine rating is the nominal power an
Line 22: Line 22:
 </blockquote> </blockquote>
  
-====Standby Power====+====:: ESP :: Standby Power====
 <blockquote John Deere, Generator Drive Engine Specifications> <blockquote John Deere, Generator Drive Engine Specifications>
 The standby gen-set engine rating is the nominal engine power The standby gen-set engine rating is the nominal engine power
Line 32: Line 32:
 ISO 8528-1. ISO 8528-1.
 </blockquote> </blockquote>
 +
 +====:: COP :: Continuous Power or Baseload Power === 
 +<blockquote>
 +Applicable for supplying power continuously 
 +to a constant 100% load for unlimited
 +hours. Continuous Power (COP) in
 +accordance with ISO 8528, ISO 3046,
 +AS 2789, DIN6271 and BS 5514.
 +</blockquote>
 +
 +---- 
 +=====Power Rating Application Guidelines: Summary=== 
 +^ Power Rating                        ^  Normal Operating Mode Limitations                                                                   ^^  Peak Operating Mode Limitations                                      ^^ Typical Application                                                                     ^
 +^ :::                                 ^ Maximum Average Load                                            ^ Maximum Operating \\ Time per Year  ^ Maximum Power                     ^ Maximum Operating\\ Time per Year  ^ :::                                                                                     ^
 +^ Standby Power                       | 80% of Standby Power                                            | 200 hours                           | Standby Power                     | 25 hours                           | Emergency Standby                                                                       |
 +^ Prime Power \\  - Unlimited Time -  | 70% of Prime Power\\ (during any 250 hour \\ operating period)  | Unlimited                           | (1) Prime Power + 10%             | 25 hours                           | Unreliable Utility Power \\ Marine Auxiliary \\ Head-end equipment \\ Rental equipment  |
 +^ :::                                 | :::                                                             | :::                                 | (2) Prime Power                   | 500 hours                          | :::                                                                                     |
 +^ Prime Power \\ - Limited Time -     | 100% of Prime Power                                             | 750 hours                           | Prime Power                       | 750 hours                          | Peak Shaving \\ Utility Power Curtailment                                               |
 +^ Continuous Power                    | 100% of Continuous Power                                        | Unlimited                           | Continuous Power                  | Unlimited                          | Utility Power \\ Electric Marine Propulsion \\ Cogeneration                             |
 +
 +
 +
ge/prime-vs-standby.1359045611.txt.gz · Last modified: 2018/05/28 22:28 (external edit)