- | ======Estimating Fault Current Availability===== | ||
- | |||
- | Short-circuit current available in bolted-fault conditions. The system fault current is the sum of all connected source fault currents. | ||
- | |||
- | =====Utility Transformers==== | ||
- | |||
- | For utility transformers, | ||
- | \\ | ||
- | |||
- | ===Three-Phase Fault== | ||
- | <WRAP col2> | ||
- | <m 14>I ~ = ~ {kVA * 1000}/ | ||
- | <m 14>I3p ~ = ~ I / {Z1}</ | ||
- | |||
- | <m 14>I3p ~=~ {kVA * 1000}/ | ||
- | </ | ||
- | \\ | ||
- | |||
- | For example, a 630kVA/ | ||
- | <WRAP col2> | ||
- | <m 14>I ~ = ~ {630kVA * 1000}/ | ||
- | |||
- | <m 14>I3p ~ = ~ 910 / 0.0576 ~ = ~ 15,833 ~ Amps</ | ||
- | </ | ||
- | \\ | ||
- | ---- | ||
- | ===Phase to Phase Fault== | ||
- | <WRAP col2> | ||
- | <m 14>Ipp ~=~ I / {(Z1 + Z2)}</ | ||
- | \\ \\ | ||
- | <m 14>Ipp ~=~ {kVA * 1000} / {V * (Z1 + Z2)}</ | ||
- | \\ \\ | ||
- | <m 14>Ipp ~=~ {630 * 1000} / {400 * (0.0576 + 0.0576)} ~=~ 13,671 ~Amps</ | ||
- | \\ | ||
- | </ | ||
- | \\ | ||
- | ---- | ||
- | ===Phase to Neutral Fault== | ||
- | <WRAP col2> | ||
- | <m 14>Ipn ~=~ {3 * I}/ {(Z0 + Z1 + Z2)}</ | ||
- | \\ \\ | ||
- | <m 14>Ipn ~=~ {3*VA} / {sqrt{3} * V * (Z0 + Z1 + Z2)}</ | ||
- | \\ \\ | ||
- | <m 14>Ipn ~=~ {3 * (630 * 1000)}/ | ||
- | \\ | ||
- | </ | ||
- | \\ | ||
- | ---- | ||
- | \\ | ||
- | |||
- | <WRAP center 650px> | ||
- | | **Voltage: | ||
- | | <m 14> | ||
- | | **Positive Sequence Impedance: | ||
- | | **Negative Sequence Impedance: | ||
- | | **Zero Sequence Impedance: | ||
- | </ | ||
- | |||
- | =====Generators==== | ||
- | |||
- | The three-phase bolted fault current from a generator is roughly the rated ampacity of the generator, divided by the subtransient reactance of the machine at that rating. Subtransient reactance is noted on the manufacturer' | ||
- | |||
- | ===Three-Phase Bolted Fault=== | ||
- | For example, with a 200kW/ | ||
- | |||
- | \\ | ||
- | <WRAP col2> | ||
- | <m 14>I ~ = ~ {kW * 1000}/ | ||
- | \\ \\ | ||
- | <m 14>I ~ = ~ {200kW * 1000}/ | ||
- | \\ | ||
- | </ | ||
- | \\ | ||
- | <WRAP col2> | ||
- | <m 14>I3p ~ = ~ I / {X prime prime d}</ | ||
- | \\ | ||
- | <m 14>I3p ~ = ~ 300 / 0.12 ~ = ~ 2,500 ~ Amps</ | ||
- | </ | ||
- | \\ | ||
- | |||
- | ===Single Phase - Neutral Bolted Fault=== | ||
- | A single phase-neutral bolted fault may have higher short-circuit current than a Line-Line fault on wye-connected generators with 2/3 pitch windings. The product of the three phase currents divided by the sum of the Subtransient Reactance (// | ||
- | |||
- | For a generator with full load current at 200 kW, 480 volts, 60 Hz of 300 amps: | ||
- | |||
- | <WRAP col2> | ||
- | * Subtransient Reactance (// | ||
- | * Negative Sequence Reactance (// | ||
- | * Zero Sequence Reactance (// | ||
- | * //Note: " | ||
- | \\ | ||
- | |||
- | <m 14>Ipn ~=~ {3 * I} / {X prime prime d + X2 + X0}</ | ||
- | \\ \\ \\ \\ | ||
- | |||
- | |||
- | <m 14>Ipn ~=~ {3 * 300Amps}/ | ||
- | </ | ||
- | \\ | ||
- | |||
- | |||
- | ---- | ||
- | ===References=== | ||
- | |||
- | * [[https:// | ||
- | * [[https:// | ||
- | * [[https:// | ||