This shows you the differences between two versions of the page.
| Previous revision | |||
| — | reference:awg-iec-wire [2025/07/23 22:40] (current) – [AWG-IEC Wire Gauges] Alan Shea | ||
|---|---|---|---|
| Line 1: | Line 1: | ||
| + | ~~NOTOC~~ | ||
| + | ======AWG-IEC Wire Gauges==== | ||
| + | American Wire Gauge (AWG) and IEC (mm< | ||
| + | |||
| + | <WRAP group> | ||
| + | <WRAP column 400px> | ||
| + | |||
| + | ^  AWG/\\ kcmil  ^  Area Circular Mils  ^  Amperes  | ||
| + | ^ ::: ^ ::: ^ TW/UF (60C) ^ THHW (75C) ^ THHN (90C) ^ ::: ^ | ||
| + | |  18            |  1620                |  --            | ||
| + | |  16            |  2580                |  --            | ||
| + | |  14*            | ||
| + | |  12*            | ||
| + | |  10*            | ||
| + | |  8              | ||
| + | |  6              | ||
| + | |  4              | ||
| + | |  3              | ||
| + | |  2              | ||
| + | |  1              | ||
| + | |  1/0            | ||
| + | |  2/0            | ||
| + | |  3/0            | ||
| + | |  4/0            | ||
| + | |  250            | ||
| + | |  300            | ||
| + | |  350            | ||
| + | |  400            | ||
| + | |  500            | ||
| + | |  600            | ||
| + | |  700            | ||
| + | |  750            | ||
| + | |  800            | ||
| + | |  900            | ||
| + | |  1000          |  1000, | ||
| + | |||
| + | * Maximum overcurrent protection: \\ #14 = 15A, #12 = 20A, #10 = 30A | ||
| + | |||
| + | //NEC 2007, Chap 9, Table 8, \\ via Ugly's Electrical Ref 2008, pp71, 73// | ||
| + | </ | ||
| + | |||
| + | <WRAP column 270px> | ||
| + | ^  IEC mm2  ^  Circular Mils  ^  Amperes  | ||
| + | | :::       | :::              | ||
| + | |  0.5      |  987            |  --                  | ||
| + | |  0.75      | ||
| + | |  1.5      |  2961            | ||
| + | |  2.5      |  4935            | ||
| + | |  4        |  7896            | ||
| + | |  6        |  11, | ||
| + | |  10        | ||
| + | |  16        | ||
| + | |  25        | ||
| + | |  35        | ||
| + | |  50        | ||
| + | |  70        | ||
| + | |  95        | ||
| + | |  120      |  236, | ||
| + | |  150      |  296, | ||
| + | |  185      |  365, | ||
| + | |  240      |  473, | ||
| + | |  300      |  592, | ||
| + | |||
| + | * //IEC 60364-5-52, Table A.52.4// | ||
| + |   * Fig. G20, https:// | ||
| + | </ | ||
| + | <WRAP clear></ | ||
| + | <WRAP column 450px> | ||
| + | |||
| + | ===Short-time Withstand Rating=== | ||
| + | Copper conductors and bolted connections withstand rating: | ||
| + | * 1 Ampere for 5 seconds per: | ||
| + | * 30 circular mils (bare wire) | ||
| + | * 42.25 circular mils (75°C insulated wire) | ||
| + | //NEC 250-94, 250-95// | ||
| + | |||
| + | ===Conversions=== | ||
| + | * kcmil = Square Inches x 1273 | ||
| + | * kcmil = Square Millimeters x 1.974 | ||
| + | * mm2 = kcmil x 0.5067 | ||
| + | |||
| + | //2007 Erico Cadweld Catalog, Technical Information (page B-4)// | ||
| + | </ | ||
| + | <WRAP column 290px> | ||
| + | |||
| + | {{ : | ||
| + | </ | ||
| + | </ | ||
| + | <WRAP clear></ | ||
| + | \\ \\ | ||
| + | [[wp> | ||
| + | |||
| + | [[https:// | ||
| + | |||
| + | |||
| + | ---- | ||
| + | ===Downloads== | ||
| + |   * {{ : | ||
| + |   * {{ : | ||
| + |   * {{ : | ||
| + | |||
| + | <wrap hide> | ||