Differences

This shows you the differences between two versions of the page.

Link to this comparison view

Both sides previous revisionPrevious revision
Next revision
Previous revision
ats:inteli [2024/06/26 03:18] – [Manual Bypass] Alan Sheaats:inteli [2024/09/21 22:24] (current) – [117 ATS -- Automatic Transfer Switch-Contactor] Alan Shea
Line 8: Line 8:
 The appropriate size of motor contactors should be selected based on the load served and the genset size. The 400A frame is a good general purpose selection, but smaller or larger can substituted. Recommended source: [[https://www.factorymation.com/Contactors_Overloads_qs/Metasol-Contactors-Overloads-9-to-800A?Coil_Voltage=240V-AC-Class&Nominal_Amps=150,225,400,800|FactoryMation.com]] //(225A frame and larger have 100-240VAC/DC coils)//  The appropriate size of motor contactors should be selected based on the load served and the genset size. The 400A frame is a good general purpose selection, but smaller or larger can substituted. Recommended source: [[https://www.factorymation.com/Contactors_Overloads_qs/Metasol-Contactors-Overloads-9-to-800A?Coil_Voltage=240V-AC-Class&Nominal_Amps=150,225,400,800|FactoryMation.com]] //(225A frame and larger have 100-240VAC/DC coils)// 
  
-  * //See the discussion at [[ats:start|ATS Pro & Con]] for reasons why this may or may not be an appropriate choice for your application.// +  * //See the discussion at [[ats:start#contactor-based-atspro-con|ATS Pro & Con]] for reasons why this may or may not be an appropriate choice for your application.// 
  
 ----  ---- 
Line 125: Line 125:
  
 {{page>:warnings&nofooter}} {{page>:warnings&nofooter}}
 +
 +<WRAP center round alert 70%>
 +**DANGER:** Current transformers must be connected to a device, or short-circuited before power is applied in the circuit to be measured. Current transformers are //constant current// devices, not //constant voltage// like ordinary transformers. 
 +
 +  * **A C.T. with loose leads can have lethal voltage on the terminal, possibly over 1000V.** 
 +
 +  * **Do not disconnect a C.T. when power is present in the measured circuit!** 
 +</WRAP>
 +
ats/inteli.1719371906.txt.gz · Last modified: 2024/06/26 03:18 by Alan Shea