This shows you the differences between two versions of the page.
Both sides previous revisionPrevious revisionNext revision | Previous revision | ||
ats:relay [2024/05/25 12:28] – removed - external edit (Unknown date) 127.0.0.1 | ats:relay [2024/06/10 22:38] (current) – [Auto Mains Fail Transfer Switch :: Relay Logic] Alan Shea | ||
---|---|---|---|
Line 1: | Line 1: | ||
+ | ======Auto Mains Fail Transfer Switch :: Relay Logic ==== | ||
+ | This Auto Mains Fail or Automatic Transfer Switch uses [[https:// | ||
+ | {{ : | ||
+ | One or more [[ats: | ||
+ | |||
+ | ====Motor Contactor Selection== | ||
+ | The appropriate size of motor contactors should be selected based on the load served and the genset size. The 400A frame is a good general purpose selection, but smaller or larger can substituted. Recommended source: [[https:// | ||
+ | |||
+ | * //See the discussion at [[ats: | ||
+ | \\ | ||
+ | |||
+ | ---- | ||
+ | \\ | ||
+ | <WRAP center round alert 60%> | ||
+ | \\ | ||
+ | **See warnings below** | ||
+ | </ | ||
+ | \\ | ||
+ | ---- | ||
+ | |||
+ | =====One-Line Diagram=== | ||
+ | {{ : | ||
+ | ===Auto Mains Fail Transfer Switch -- Selector Switch== | ||
+ | <WRAP col2> | ||
+ | One-line diagram, detailed schematic/ | ||
+ | * {{ : | ||
+ | * {{ : | ||
+ | \\ | ||
+ | //(.dsn) files can be edited with [[: | ||
+ | |||
+ | </ | ||
+ | |||
+ | ====Description of Operation=== | ||
+ | Contactors K-U [13] and K-G [14] are mechanically and electrically interlocked to ensure that only one can be closed at a time. | ||
+ | |||
+ | ===Definitions== | ||
+ | * **Utility Connected: | ||
+ | * **Generator Connected: | ||
+ | * **Load Connected: | ||
+ | * **K-G [13], K-U [14]**: Utility & Generator Power Contactors, 400 Amp 3-pole | ||
+ | * **K-PHM-U [2], K-PHM-G [10]** : Phase Monitor -- Loss of phase, phase rotation, and low voltage relay | ||
+ | * **K-VM-UA [3], K-VM-GA [9]** : Over voltage relay | ||
+ | * **K-US [4], K-GS [8]** : Time Delay (Voltage stabilization) | ||
+ | * **K-U ENABLE [5]** : Time delay to ensure utility/ | ||
+ | * **K-G STOP [6]** : Generator cool-down delay | ||
+ | * **K-G START [7]** : Generator start delay after utility power failure | ||
+ | |||
+ | ===Utility Power Failure== | ||
+ | - Starting with Utility Power being supplied to the load: Contactor K-U [13] is closed, and all timers have expired.((Time delays listed are defaults, and can be adjusted as desired.)) Timer K-G STOP [6] has expired and its contacts are closed. | ||
+ | - Power is removed from the coil for K-U [13] if: | ||
+ | - Utility power fails | ||
+ | - A phase is lost or the voltage drops below the limit set by K-PHM-U [2] | ||
+ | - Voltage goes above the limit set by K-VM-UA [3] | ||
+ | - When K-U [13] opens: | ||
+ | - Load is disconnected (Preventing damage to equipment caused by low voltage.) | ||
+ | - Removes power from timer K-G START [7], which starts its timer. | ||
+ | - If Utility/ | ||
+ | - K-U [13] will close after K-US [4] delay | ||
+ | - K-G STOP [6] will time out, potentially running the genset for up to K-G STOP [6] time delay. | ||
+ | - When timer K-G START [7] expires (30 seconds), its contacts close, which causes the selected genset to begin its autostart sequence. | ||
+ | - Once the generator is supplying power: | ||
+ | - K-PHM-G [10] qualifies all phases live, phase rotation, and minimum voltage | ||
+ | - K-VM-GA [9] qualifies maximum voltage | ||
+ | - Illuminates L-G (Blue) indicating generator power is OK. | ||
+ | - K-GS [8] begins its countdown (30 seconds). | ||
+ | - K-G [14] then closes: | ||
+ | - Supplies generator power to the load | ||
+ | - Opens the neutral connection for the coil on K-U [13], preventing K-U [13] from closing by accident. | ||
+ | - Illuminates L-KG (Blue) indicating that generator is supplying the load. | ||
+ | |||
+ | ===Utility Power Return== | ||
+ | - When Utility Power returns, it must meet the constraints: | ||
+ | - K-PHM-U [2] for phase (all phases live, correct phase rotation) and minimum voltage | ||
+ | - K-VM-UA [3] maximum voltage | ||
+ | - Indicator L-U (Green) illuminates to confirm utility grid voltage is acceptable | ||
+ | - K-US [4] begins voltage stabilization delay (10 seconds). | ||
+ | - K-U ENABLE [5] begins time delay (15 minutes), which ensures: | ||
+ | - The utility grid has time to stabilize | ||
+ | - Delays adding loads to the grid after an outage | ||
+ | - Eliminates short-cycling if the grid drops again shortly after returning | ||
+ | - Provides a minimum run-time for the generator to ensure it gets up to temperature | ||
+ | - When K-U ENABLE [5] turns on, it opens the coil for K-G [14]: | ||
+ | - Disconnects load from Generator | ||
+ | - Connects neutral of K-U [13] coil | ||
+ | - K-U [13] closes immediately | ||
+ | - Connects load to Utility Grid | ||
+ | - Disables K-G [14] by disconnecting neutral of coil | ||
+ | - Illuminates L-KU (Green), indicating Utility/ | ||
+ | - Provides power to K-G STOP [6] | ||
+ | - K-G STOP [6] begins time delay (2 minutes) for Generator cool-down (running with no load) | ||
+ | - K-G START [7] turns on, disconnecting the generator auto-start signal | ||
+ | - Genset stops | ||
+ | |||
+ | ====Bill of Materials== | ||
+ | ===116 ATS -- Automatic Transfer Switch-Contactor=== | ||
+ | |||
+ | * [[https:// | ||
+ | * [[https:// | ||
+ | * [[https:// | ||
+ | * [[https:// | ||
+ | |||
+ | < | ||
+ | |||
+ | |||
+ | {{page>: |
Copyright © Alan Shea, 2011-2025